ENERGY-EFFICIENCY ECONOMICS
Terms and Definitions
Certain terms are consistently used in the fields of building
energy efficiency and financial and economic analysis. Energy
Raters must be familiar with the terminology of both fields to
properly discharge their function as energy auditors and to
understand the financial implications of the recommendations they
make to their clients. For ease of reference the two fields have
been segregated, then alphabetized below. In a few instances a
term has been included in both sections.
| Energy-Efficiency,
Energy Code and Rating System Terminology
The following terms form the basis of the nomenclature that is
used in the field of building energy efficiency. Without full
comprehension of this terminology, Raters
will not be able to converse intelligently with their clients,
program administrators or technical assistance personnel.
- Accreditation:
The process of certifying a Home Energy Rating System (HERS)
as being compliant with the national industry standard
operating procedures for Home Energy Rating System.(1)
- AFUE
(Annual Fuel Utilization Efficiency): A measurement
of the seasonal energy efficiency of gas heating equipment. It
is the annual output energy of the equipment divided by its
annual input energy, expressed in consistent units (i.e. Btu-out
per Btu-in). Thus, the resultant value of AFUE is unit less.
AFUE includes any input energy required by the pilot light but
does not include any electrical energy for fans or pumps.
- BESTEST
(Building Energy Simulation Test): A standardized
procedure developed by the National Renewable Energy
Laboratory and used to test the energy load prediction
capabilities and accuracy of software designed for use in Home
Energy Rating Systems.(2)
Florida's ENERGYGAUGE™
software has been subjected to the BESTEST procedure with
excellent results.(3)
- Btu
(British Thermal Unit): One of the two (watt-hours
is the other) standard units of measure (IP System) for the
amount of energy consumed by a process, the amount of energy
transferred from one location to another, or the amount of
embodied energy (such as the heat content of fuels).
Specifically, it is the amount of energy required to raise the
temperature of one pound of water by one degree Fahrenheit.
The term 'kBtu' stands for "kiloBtu" or 1,000 Btu.
The term of 'MBtu' stands for "MegaBtu" or 1,000,000
Btu. One Btu is equal to 0.293 watt-hours (Wh).
- Btu/h
(British Thermal Units per Hour): One of the two (watts
is the other) standard units of measure (IP System) for the
rate at which energy is used by equipment or the rate at which
energy moves from one location to another. One Btu/h is equal
to 0.293 watts (W).
- CABO
(Council of American Building Officials): A
national organization of building code officials and
interested parties which, through a national consensus
process, developed, adopted and promulgated the national Model
Energy Code (MEC).
CABO has recently become CABO International and has taken on
the administrative responsibility for the development of a
uniform international building code through an International
Code Council (ICC).
- Capacity:
The quantity of heating or cooling load that can be satisfied
by a given equipment system designed to heat or cool and
dehumidify a conditioned space or heat service hot water.
Heating and cooling capacity is normally given on equipment
nameplates in units of Btu.
The air conditioning industry often uses units of "tons"
to refer to equipment capacity. One ton of capacity equals
12,000 Btu.
- Confirmed
Rating: A Class
2 or Class
1 Rating performed on a completed construction project
that confirms the energy-efficient features of a new building
or the improvements made to an existing building.
- Construction
Documents: The set contractual documents by and
between the owner and builder of a new building for
construction, consisting of all drawings (the plans) and
written specifications that are intended to govern the
construction of the building.
- COP
(Coefficient of Performance): A measurement of the
instantaneous efficiency of heating or cooling equipment. It
represents the steady-state rate of energy output of the
equipment divided by the steady-state rate of energy input to
the equipment, expressed in consistent units (i.e. watts-out
per watts-in or Btu/h-out
per Btu/h-in). Thus, the resultant value of COP is unit less.
Most vapor-compression heating and cooling equipment has COPs
greater than unity. That means it delivers more heat energy
than it consumes.
- EEM
(Energy Efficient Mortgage): Specifically, a home
mortgage for which the borrower's qualifying debt-to-income
and housing
expense-to-income ratios have been increased
("stretched") by 2% because the home meets or
exceeds the minimum standards of the Council of American
Building Officials (CABO)
1992 version of the Model Energy Code (MEC).
This so-called "stretch" mortgage results from
provisions of the Cranston-Gonzalez National Affordable
Housing Act, and is refined by the U.S. Energy Policy Act of
1992 (EPAct).
The EEM is nationally underwritten by Fannie
Mae, Freddie
Mac and the Federal Housing Administration (FHA).
NOTE: This term is often used
generically to refer to any home mortgage for which the
underwriting guidelines have been relaxed specifically for
energy efficiency features, or for which any form of financing
incentive is given for energy efficiency.
- EER
(Energy Efficiency Ratio): A measurement of the
instantaneous energy efficiency of cooling equipment. It
normally is used only for electric air conditioning equipment.
EER is the steady-state rate of heat energy removal by the
equipment in Btu/h
divided by the steady-state rate of energy input to the
equipment in watts.
Thus, the resultant value for EER has units of Btu/Wh.
The EER of a given system is always higher than the COP of
that system by a factor equal to the number of Btu/h in a
watt, or 3.413.
- EIM
(Energy Improvement Mortgage): A home improvement
mortgage that is given specifically for energy efficiency
improvements to the property.
- EF (Energy
Factor): A standardized measurement of the annual
energy efficiency of water heating systems. It is the annual
hot water energy delivered to a standard hot water load
divided by the total annual purchased hot water energy input
in consistent units (Wh-out
per Wh-in or Btu-out
per Btu-in). Thus, the resultant value of EF is unitless. EF
is determined by a standardized US Department of Energy
procedure. Florida has developed EFs for almost all types of
water heating systems, including solar water heating system.
- Energy
(use): The quantity of electricity, gas or other
fuel required by the building equipment to satisfy the
building heating, cooling and hot water loads imposed on that
equipment by its thermostats plus the energy required to
satisfy any other energy service requirements (lighting,
refrigeration, cooking, etc.) of the building (see also the
definitions of load
and thermostat).
- Energy
Audit: A site inventory and descriptive record of
features impacting the energy use in a building. This
includes, but is not limited to: all building component
descriptions (locations, areas, orientations, construction
attributes and energy transfer characteristics); all energy
using equipment and appliance descriptions (use, make, model,
capacity, efficiency and fuel type) and all energy features.
- ENERGYGAUGE:
Florida's computerized tool for energy code compliance and
energy rating computations, including combined energy,
economic and financial analysis.
- ENERGY
STAR® Home: A home,
certified by the US Environmental Protection Agency (EPA),
that is at least 30% more energy efficient than the minimum
national standard for home energy efficiency as specified by
the 1992 CABOMEC.
EPA has a number of partners and allies in its ENERGY
STAR homes program and homes that
qualify for ENERGY STAR
certification through EPA are eligible for mortgage financing
incentives through EPA's mortgage banking allies.
Qualification for the ENERGY STAR
home label requires a HERS
score of 86 or greater. In Florida, this means that the
home must receive a confirmed Rating by a certified Class
2 or Class
1 Rater.
ENERGY STAR is a
registered trademark of the U.S. EPA.
- EPAct
(Energy Policy Act of 1992): An Act of the 1992
U.S. Congress which, among other things, requires the
Secretary of DOE to issue voluntary guidelines for residential
energy efficiency ratings and requires the Secretary of HUD to
establish an Energy
Efficient Mortgage Pilot Program. The Act also requires
state governments to "certify to the Secretary (of U.S.
DOE) that it has reviewed the provisions of its residential
building codes regarding energy efficiency and made a
determination as to whether it is appropriate for such state
to revise such residential building code provisions to meet or
exceed the CABOModel
Energy Code, 1992."
- Existing
Residence (or Home): A Completed residential
occupancy building, including residential occupancy dwellings
in mixed occupancy buildings for which a certificate of
occupancy, or equivalent approval for occupancy, has been
issued.
- Fannie
Mae (FNMA - Federal National Mortgage Association):
A private, tax-paying corporation chartered by the U.S.
Congress to provide financial products and services that
increase the availability of housing for low-, moderate-, and
middle-income Americans. Fannie Mae is the nation's largest
corporation with $366 billion in assets and $674 billion in
mortgage backed securities as of 1998. It is traded on the New
York Stock Exchange (FNM), has 240,000 shareholders, and is
part of Standard & Poor's 500 index. Fannie Mae
constitutes the largest part of the nation's secondary
mortgage market. Fannie Mae effectively increases the money
supply in the primary mortgage market by purchasing (up to
their prescribed limit of $214,600 as of 1/1/97), packaging,
guaranteeing and selling conventional residential mortgages
(as well as those insured by FHA
or guaranteed by VA) to investors as Mortgage Backed
Securities (MBS).
- FHA
(Federal Housing Administration): A division of the
Department of Housing and Urban Development (HUD). FHA's main
activity is the insurance of residential mortgage loans made
by private lenders. FHA neither buys nor originates mortgages,
however, through its insurance function it sets standards for
mortgage underwriting. FHA insured loans are open to all
qualified home purchasers of moderately priced homes (up to a
maximum loan value of $155,250 as of 1/1/96). FHA requires a
Mortgage Insurance Premium (MIP)
of up to 2.25 percent of the loan amount (paid at closing) to
insure the loan with FHA. In addition, FHA mortgage insurance
requires an annual insurance fee of up to 0.5 percent of the
loan amount, paid in monthly installments. The lower the down
payment, the more years the mortgage insurance fee must be
paid.
- Freddie
Mac (FHLMC - Federal Home Loan Mortgage Corporation):
A stockholder-owned organization, chartered by the U.S.
Congress to increase the supply of mortgage funds. Freddie Mac
purchases conventional mortgages from insured depository
institutions and HUD-approved mortgage bankers. It does not
originate loans but it provides a secondary market for the
mortgage industry by purchasing their mortgages, packaging
them into securities that are guaranteed by Freddie Mac, and
selling them to investors.
- HERS
(Home Energy Rating System): A standardized system
for rating the energy-efficiency of residential buildings.
Home Energy Rating Systems are currently governed by two
national industry standards: 1) the HERS Council Guidelines,(4)
which prescribe the accepted methods and procedures for rating
a home, and 2) the Mortgage Industry HERS Accreditation
Procedures,(1)
which prescribe the methods and procedures for the
certification of Home Energy Rating System by individual state
governments and the national home mortgage industry. In
Florida, HERS are additionally governed by an Act of the State
Legislature(5)
that requires the Florida Department of Community Affairs (DCA)
"to adopt, update and maintain a statewide uniform
building energy-efficiency rating system" through
rulemaking.(6)
- HERS
Energy-Efficient Reference Home (EERH): The EERH is
a geometric "twin" to the home being evaluated (Rated
Home) and is configured to be minimally compliant with the
National Council of American Building Officials (CABO)
Model Energy Code (MEC)
of 1992.
- HERS
Provider: An individual or organization responsible
for the operation and management of a Home Energy Rating
System. By Florida Statute, the sole HERS provider authorized
to perform this function in the State is the Florida
Department of Community Affairs.
- HERS Rater:
An individual, certified by the State of Florida, to perform
residential Building Energy Efficiency Ratings in the Class
for which the Rater is certified. There are three classes of
residential Rater certification: Class
3 - requiring the certified capability to complete Ratings
based on construction documents; Class
2 - requiring the certified capability to complete Ratings
based on site energy audits; and Class
1 - requiring the certified capability to complete Ratings
based on site energy audits and performance tests.
- HERS Score:
A numeric value between 0 and 100 indicating the relative
energy efficiency of a given home as compared with the HERS
Energy-Efficient Reference Home (EERH)
as specified by the HERS Council Guidelines. The greater the
score, the more efficient the home. A home with zero energy
use for the rated energy uses (heating, cooling and hot water
only) scores 100 and the HERS Energy-Efficient Reference Home
scores 80.
- HSPF
(Heating Season Performance Factor): A measurement
of the seasonal efficiency of an electric heat pump using a
standard heating load and outdoor climate profile over a
standard heating season. It represents the total seasonal
heating output in Btu
divided by the total seasonal electric power input in
watt-hours (Wh).
Thus, the resultant value for HSPF has units of Btu/Wh.
- Improvement
Analysis: A written calculation of the
cost-effectiveness of various options to improve the energy
efficiency of a building, including an explicit report on the
assumed financing rate and lives of the measures used in the
calculation and consideration of interactions between
energy-saving measures.
- Load:
The quantity of heat that must be added to or removed from the
building (or the hot water tank) to satisfy specific levels of
service - in other words, to keep the space temperature or hot
water temperature at a specified thermostat setting (see also
the definitions of energy and thermostat).
- MEC
(Model Energy Code): A "model" national
standard for residential energy efficiency. The MEC was
developed through a national consensus process by the Council
of American Building Officials (CABO)
and is the accepted national minimum efficiency standard for
residential construction. Since MEC is a model code, it does
not have the "force of law" unless and until it is
adopted by the local code authority. Nonetheless, MEC is used
as the basis for many, if not most, of the energy efficiency
criteria employed in the U.S. marketplace. By virtue of its
reference in the 1992 U.S. Energy Policy Act (EPAct),
the MEC is used as the national standard for determining
Energy Efficient Mortgage (EEM)
qualification, and it serves as the national "reference
point" used by Home Energy Rating Systems (HERS)
in the determination of energy ratings for homes.
- NAECA
(National Appliance Energy Conservation Act): An
act of the 1987 U.S. Congress requiring the U.S. Department of
Energy (DOE) to establish minimum performance efficiency
standards for residential equipment and appliances sold within
the United States.
- New
Residence (or Home): A residential occupancy
buildings, including new residential occupancy dwellings in
mixed occupancy buildings, that is permitted for construction
after July 1, 1994, but has not yet been issued a certificate
of occupancy.
- Performance
Test: An on-site measurement of the energy
performance of a building energy feature or an energy using
device conducted in accordance with pre-defined testing and
measurement protocols and analysis and computation methods.
Such protocols and methods may be defined by national
consensus standards like those of the American Society of
Heating, Refrigerating and Air Conditioning Engineers (ASHRAE)
and the American Society for Test and Measurement (ASTM), or
as modified or defined and adopted by the Department of
Community Affairs, Office of Codes and Standards.
- Point
Multiplier: A colloquial term for load correlation
coefficient. A numeric value that when multiplied by the
number of units of a given building component will yield the
overall contribution of that component to the annual heating,
cooling or hot water load for the building. Florida's energy
code for residential buildings uses summer point multipliers (SPM),
winter point multipliers (WPM) and hot water point multipliers
(HWPM) to compute the various annual loads for the residence.
- Projected
Rating: A rating
of any Class performed prior to the construction of a new
building or prior to implementation of energy-efficiency
improvements to an existing building.
- Rated Home:
The specific residence that is evaluated by an energy rating.
- Rater:
An individual, certified by the State of Florida, to perform
Building Energy Efficiency Ratings
for the building type and in the rating Class
for which the Rater
is certified. There are three classes of residential Rater
certification: Class
3 - requiring the certified capability to complete Ratings
based on construction documents; Class
2 - requiring the certified capability to complete Ratings
based on site energy audits; and Class
1 - requiring the certified capability to complete Ratings
based on site energy audits and performance tests. (See also HERS
Rater.)
- Rating
(Building Energy-Efficiency Rating): A set of
documents comprising a registered Rating
Guide (DCA Form 11) plus any appropriate improvement
recommendations, economic analysis, and financial forms that
are required to complete an energy efficient mortgage
application for the rated building. There are two types of
Rating: Projected
Ratings and Confirmed
Ratings. Projected ratings are reserved for Ratings Based
on Plans (new
buildings) and Ratings for Improvement (existing
or new buildings). Confirmed Ratings are reserved for final
documentation of completed new buildings or for documentation
of improvements to existing buildings.
- Rating
Class: The category of a Rating,
based on the source of the input data which are used to
compute the energy and cost estimates of the Rating, and
consisting of the following three categories:
- Class
1 Rating - An energy rating,
conducted using site energy audit and performance test
data as the sources for the input data on which the rating
is based.
- Class
2 Rating - An energy rating
conducted using site energy audit data as the source for
the input data on which the rating is based.
- Class
3 Rating - A projected
energy rating
reserved for new buildings and clearly labeled as a
"projected rating based on plans" that is
conducted using construction documents as the sources for
the input data on which the rating is based.
- Rating
Guide: A completed and signed DCA Form 11 providing
the following information: the type of rating
(projected
or confirmed);
the registration number for the Rating; the estimated energy
use and energy cost for the building and its associated energy
end-uses; the name, signature and certification number of the Rater;
a comparative analysis of the building's energy-efficiency
relative to other, similar buildings of the same type, located
in the same climate; the national HERS
Score for the building; and information on how the Rating
should be interpreted.
- R-value:
A numeric value defining the resistance to heat transfer of
the full thickness of a material or composite of materials.
R-value is the reciprocal of conductance (C) and has units of
hr/Btu-ft2-oF. Important Note on
R-values: The input values required by Florida's code and
rating system calculation procedures are for the R-value of
the designated insulation product only - not the R-value of
the entire building component assembly.
- SEER
(Seasonal Energy Efficiency Ratio): A measurement
similar to HSPF
except that it measures the seasonal cooling efficiency of an
electric air conditioner or heat pump using a standard cooling
load and outdoor climate profile over a standard cooling
season. It represents the total seasonal cooling output in Btu
divided by the total seasonal electric input in watt-hours (Wh).
Thus, the resultant value for SEER has units of Btu/Wh.
- Shading
Coefficient (SC): The ratio of the total solar heat
admittance of a given glazing product relative to the solar
heat admittance of " double-strength, clear glass at
normal solar incidence (i.e. perpendicular to the glazing
surface).
- Solar
Heat Gain Coefficient (SHGC): The ratio of the
total solar heat admittance of a given window product relative
to the solar heat incident on the projected window surface at
normal solar incidence (i.e. perpendicular to the glazing
surface).
- Thermostat:
A control device that measures the temperature of the air in a
home or the water in a hot water tank and activates the
heating or cooling equipment to cause the air or water
temperature to remain at a pre-specified value, normally
called the set point temperature (see also the definitions of
load and energy).
- Ton(s):
A term used primarily by the air conditioning industry to
characterize the cooling capacity
of air conditioning equipment. One ton equals 12,000 Btu.
- U-value:
The total thermal conductance of a building assembly (wall,
floor, ceiling, etc.), including the indoor and outdoor
air-film resistances of the assembly. The U-value when
multiplied by the effective temperature difference between the
indoors and outdoors, including the effects of solar and sky
radiation (the "sol-air" temperature) where
appropriate, will yield the normalized (per unit area) heat
flow across that building composite. The units of U-value are
Btu/hr-ft2-oF.
- W (watt):
One of two (Btu/h
is the other) standard units of measure (SI System) for the
rate at which energy is consumed by equipment or the rate at
which energy moves from one location to another. It is also
the standard unit of measure for electrical power. The term
'kW' stands for "kilowatt" or 1,000 watts. The term
'MW' stands for "Megawatt" or 1,000,000 watts. One
watt is equal to 3.413 Btu/h.
- Wh
(watt-hour): One of two (Btu
is the other) standard units of measure (SI system) for the
amount of energy that is consumed by equipment, the amount of
embodied energy, or the amount of energy moved from one
location to another. It is also the standard unit of measure
for electrical use. The term 'kWh' stands for
"kilowatt-hour" or 1,000 watt-hours. The term 'MWh'
stands for "Megawatt-hours" or 1,000,000 watt-hours.
One watt-hour is equal to 3.413 Btu.
Additional energy and energy code terminology of interest is
defined in Chapter 2 of the Florida Energy Code.(7)
Economic,
Financial and Real Estate Terminology
The following terms are basic to understanding and using energy
ratings in the financial marketplace. The enhanced version of ENERGYGAUGE
is designed to perform analysis and produce results and reports
that are useful in obtaining home mortgages. Without a full
understanding of the terms contained in this section, Raters will
not be able to take advantage of these powerful marketplace
capabilities or provide these important services to their
clients.
- Adjustable
Rate Mortgage: A secured loan in which the interest
rate is adjusted periodically based on a preselected index.
Also sometimes known as the renegotiable rate mortgage, the
variable rate mortgage or the Canadian rollover mortgage.
- Analysis
with Replacement: An Improvement
Analysis that includes the replacement cost of
energy-efficient equipment whose useful life is exceeded
during the analysis period. The cost of replacing the
energy-efficient equipment, escalated at the general
inflation rate, is added to the periodic cash
flow stream the period following the end of its useful life.
- Appraisal
or Appraised Value: An estimate of the value of
property, made by a qualified professional called an
"appraiser."
- Assessment
or Assessed Value: The value placed on real
property (a building and its grounds) by the local property
tax authority.
- Cost/Assessment:
The ratio of the cost (or appraised value) of a building with
respect to its assessed value. The cost to assessment ratio is
normally less than 1.0 and is defaulted to 0.80 in the
financial section of ENERGYGAUGE.
This value is used to determine the basis for ad valorem
(property) taxes on the property for ENERGYGAUGE
financial analysis.
- Cash Flow:
Periodic money stream(s) resulting from an economic decision
that are expected to continue into the future. For example,
rent payments, mortgage payments, taxes, etc. By convention,
incoming cash flows (revenues) are positive and outgoing cash
flows (payments) are negative. ENERGYGAUGE
calculates the cash flow for each individual economic
component of the analysis, for each year of the analysis
period.
- Cash
Flow Schedule: A table of cash flows that includes
each of the periodic money streams associated with an economic
decision.
- Current
Salvage: The salvage value of an existing home
measure that will be replaced with a more efficient measure.
Typically this value will be zero. However, for example, if an
air conditioner is replaced with a more efficient one and the
original unit has a useful life and can be sold for $300, then
$300 is the Current Salvage value.
- Debt-to-Income
Ratio: The ratio, expressed as a percentage, which
results when a borrower's total monthly payment obligations on
long-term debt are divided by their gross monthly income. This
is one of two ratios (housing
expense-to-income ratio being the other) used by the
mortgage industry to determine if a prospective borrower
qualifies (meets the underwriting
guidelines) for a specific home mortgage. Fannie
Mae, Freddie
Mac and FHA
underwriting guidelines set an upper limit of 36% on this
value for conventional loans but increase
("stretch") the ratio by 2% for qualifying Energy
Efficient Mortgages.
- Discount
Rate: The interest rate reflecting the time value
of money that is used to convert cash
flows occurring at different times to a common time (e.g.
to convert future
values to present
values and visa versa). The discount rate represents the
opportunity cost of money and is often selected as the
after-tax rate of return on an alternative investment or the
cost of borrowing money. ENERGYGAUGE
uses a real discount rate as opposed to a nominal (or market)
discount rate. In general, the nominal discount rate is
equivalent to the real discount rate increased by the personal
income tax burden plus the general inflation rate. The default
value used by ENERGYGAUGE
for the discount rate is 5%, real. ENERGYGAUGE
uses a default personal income tax rate of 28% and default
general inflation rate of 3%, equating to default market
discount rate about 10%, nominal.
- ECM
(Energy Conservation Measure): An individual
building component or product that directly impacts energy use
in a building and has a set of differentiable energy
performance factors that can be arranged into a table or list.
For example, wall insulation is a measure that will impact
heat transfer to and from a building, and there is some list
of wall measures that are differentiated by insulation R-value
that define the possible walls that can be incorporated into a
building. ENERGYGAUGE
uses ECM tables to define and store the economic data
associated with building energy efficiency alternatives.
- ECM
Lifetime: The useful lifetime of an energy
conservation measure.
- EEM
(Energy Efficient Mortgage): Specifically, a home
mortgage for which the borrower's qualifying debt-to-income
and housing expense-to-income ratios have been increased
("stretched") by 2% because the home meets or
exceeds the minimum standards of the Council of American
Building Officials (CABO)
1992 version of the Model Energy Code (MEC).
This so-called "stretch" mortgage results from
provisions of the Cranston-Gonzalez National Affordable
Housing Act, and is refined by the U.S. Energy Policy Act (EPAct)
of 1992. The EEM is nationally underwritten by Fannie
Mae, Freddie
Mac and the Federal Housing Administration (FHA).
NOTE: This term is often used
generically to refer to any home mortgage for which the
underwriting guidelines have been relaxed specifically for
energy efficiency features, or for which any form of financing
incentive is given for energy efficiency.
- EIM
(Energy Improvement Mortgage): A home improvement
mortgage that is given specifically for energy efficiency
improvements to the property.
- ENERGYGAUGE:
Florida's computerized tool for energy code compliance and
energy rating computations, including combined energy,
economic and financial analysis. (Click
here to go to a seperate web page dedicated to ENERGYGAUGE.)
- End
of Life Salvage: The salvage value of a measure at
the end of its useful life. Typically, this value will be $0.
For an economic analysis in which the useful life of a measure
is not reached at the end of the analysis period, ENERGYGAUGE
will calculate a salvage value for the remaining life of the
measure using straight-line depreciation. ENERGYGAUGE
will include this salvage value in the cash flow schedule and
in the savings to investment ratio and internal rate of return
calculations.
- Energy
Savings Goal: A user-defined level of building
energy efficiency which is used by ENERGYGAUGE's
automatic optimization
feature as the point at which the analysis will cease.
- Fixed
Rate Mortgage: A secured loan in which the interest
rate has the same value for the life of the loan.
- Fuel
Price Inflation Rate: The annual increase in fuel
price as a percent of its present value. ENERGYGAUGE
uses this value to escalate fuel price in its economic and
financial analysis procedures. The ENERGYGAUGE
default value is 3%, the same as the default value for the
general inflation rate, making the default increase in fuel
cost relative to other goods and services equal to zero.
- Future
Value (FV): Monies accruing in the future that have
not been discounted to account for the fact that they will be
worth less in the future than they are today.
- General
Inflation Rate: The annual increase in the price of
goods and services as a percent of their present price. ENERGYGAUGE
uses this value to escalate the cost of maintenance
and the cost of ECM
replacements in its financial and economic analysis
procedures. The ENERGYGAUGE
default value for the general inflation rate is 3%. Increases
in fuel prices are computed separately using the fuel price
escalation rate, which is also defaulted to 3% in ENERGYGAUGE.
- Housing
Expense-to-Income Ratio: The ratio, expressed as a
percentage, which results when a borrower's total monthly
housing expenses (P.I.T.I.)
are divided by their gross monthly income. This is one of two
ratios (debt-to-income
ratio being the other) used by the mortgage industry to
determine if a prospective borrower qualifies (meets the
underwriting guidelines) for a specific home mortgage. Fannie
Mae, Freddie
Mac and FHA
underwriting
guidelines set an upper limit of 28% on this value for
conventional loans but increase ("stretch") the
ratio by 2% for qualifying Energy
Efficient Mortgages.
- Improvement
Analysis: A written calculation of the
cost-effectiveness of various options to improve the energy
efficiency of a building, including an explicit report on the
assumed financing rate and lives of the measures used in the
calculation and consideration of interactions between
energy-saving measures.
- Income
Tax Rate: The marginal rate at which personal
income is taxed by the federal government. ENERGYGAUGE
uses this number to compute income tax impacts associated with
mortgage interest payments.
- Internal
Rate of Return (IRR): The present
value of the net
cash flow stream expressed as an annual percentage growth
rate of the initial investment (i.e. the annual compound
interest rate required to produce the same result as the
evaluated investment). ENERGYGAUGE
includes all taxes in its net cash flow stream so the IRR
given by ENERGYGAUGE
is an after-tax rate of return.
- Loan-to-value
Ratio (LTV): The total amount of the mortgage
loan divided by the appraised
value of the property that secures the mortgage.
- Maintenance
Cost: The cost of keeping an ECM
in good operating condition. ENERGYGAUGE
uses this cost to determine the differential cost of
maintaining one measure over another. Unless the maintenance
cost of one ECM in a list is greater than the maintenance cost
of the others, there is no need to enter maintenance costs in
the ECM list because the incremental cost of selecting one
measure compared to the others will always be $0. In general,
there are only a few measures in an ECM list that have a
differentiated maintenance costs. Therefore, it is simplest to
enter only the incremental cost for any measures that have a
differentiated maintenance cost.
- Mortgage
Note: A written agreement to repay a loan. The
agreement is secured by a mortgage, serves as proof of
indebtedness, and states the manner in which the debt shall be
paid. The note states the actual amount of the debt that the
mortgage secures and renders the mortgagor personally
responsible for repayment.
- Mortgage
Down Payment: Money paid by the borrower to make up
the difference between the purchase price and the loan amount.
- Mortgage
Interest Rate: The price charged for borrowing
money expressed as a percentage of the unpaid loan balance.
- Mortgage
Insurance Premium (MIP): The payment made by a
borrower to the lender for transmittal to HUD to help defray
the cost of the FHA
mortgage insurance program and to provide a reserve fund to
protect lenders against loss in insured mortgage transactions.
In FHA insured mortgages this represents a payment of 2.25% of
the loan principle at closing plus an annual rate of one-half
of one percent paid by the mortgagor on a monthly basis.
- Mortgage
Points: A point is equal to one percent of the
principal amount of the mortgage. Lenders frequently charge
points for both fixed-rate and adjustable-rate mortgages to
cover loan origination costs and to increase the yield on the
mortgage. These points normally are collected at closing and
may be paid by the buyer (borrower) or the seller, or may be
split between them.
- Mortgage
Principal: The amount of money owed by the borrower
to the lender, and the amount used to compute the periodic
interest payments on simple interest loans. The principal
normally decreases during the life of a simple interest
mortgage. However, for negative amortization mortgages it will
increase over time and for interest only loans it does not
change.
- Net
Cash Flow: The sum of the positive (revenues) and
negative (expenditures) monies accruing during each period of
an economic analysis (i.e. the total revenues minus the total
expenditures for each period of the economic analysis,
normally expressed in future
value dollars).
- Net
Present Value (NPV): The present
value of all saving (revenue) streams less the present
value of all cost (investment) streams.
- Optimization:
A energy analysis and economic evaluation process that seeks
to determine the most cost-effective means of achieving a
stated energy-efficiency or energy use goal.
- P.I.T.I.:
An abbreviation which stands for principal, interest, taxes,
and insurance. These generally represent a borrower's total
monthly payment obligations on a home loan. The taxes and
insurance portion are paid monthly to an impound or escrow
account and may be adjusted annually to reflect changes in the
cost of each.
- Present
Value (PV): Monies accruing in the future that have
been discounted to account for the fact that those monies will
be worth less in the future than they are today.
- Present
Worth (PW): The same as Net Present Value (NPV).
The present value of all saving (revenue) streams less the
present value of all cost (investment) streams.
- Private
Mortgage Insurance (PMI): Insurance that
protects a lender from loan losses in the event of default. In
most cases, PMI is used to insure the amount of a loan in
excess of an 80 percent loan-to-value ratio (LTV).
- Property
Tax Rate: The rate at which real property ownership
is taxed by the local ad valorem taxing authority.
- Ranking
Method: The economic criteria by which energy
conservation measures are ordered in an ENERGYGAUGEoptimization
analysis. The user-selectable ranking methods available in ENERGYGAUGE
are as follows:
- Simple
Payback -- will minimize the added first costs
for the improvements with respect to the achieved energy savings.
- Net Present Value of Savings
-- will maximize the net
present value (present worth) of the energy savings
over the life of the mortgage or other specified period.
- Savings to Investment Ratio (SIR)
-- will maximize the net present value of energy savings
with respect to the net present value of the added first costs
(investment) over the life of the mortgage or other
specified period.
- Internal Rate of Return on
Investment (IRR)
-- will maximize the rate at which the added first costs
(investment) for the energy-efficiency improvements return
savings
over the life of the mortgage or other specified period.
- 1st Year Cash Flow based on
Mortgage -- will maximize the net first year cash
flow to the home owner as a function of the mortgage
term and interest
rate.
- Savings:
The reduction in operating (energy) cost that results from an
improvement in building energy efficiency.
- Saving
to Investment Ratio (SIR): The ratio of the present
value of an energy saving
stream with respect to the present value of the cost
of making the energy efficiency improvements.
- Simple
payback: The number of years needed to pay for
energy efficiency improvements using the energy cost savings
that accrue annually from those improvements. The initial cost
of the improvements divided by the annual energy cost savings
from those improvements.
- Upgrade
Cost: The price that must be paid to install an
energy conservation measure into a building. If the building
is "new" (i.e. has not yet been constructed), then
the cost is equal to the cost of the improved measure minus
the cost of the minimum standard measure. If the building
already exists, then the cost is equal to the cost of the
measure minus the current salvage value for the existing
measure.
- Underwriting
Guidelines: The set of procedures and criteria used
by lending institutions to determine if it is in their best
interest to originate (primary lenders) or purchase (secondary
lenders) a specific mortgage.
- Mortgage Industry National
Accreditation Procedures for Home Energy Rating Systems,
June 1998. Residential Energy Services Network (RESNET),
Oceanside, CA; and National Association of State Energy
Officials (NASEO), Washington DC.
- Judkoff, R. and J. Neymark, August 1997.
"Home Energy Rating System Building Energy Simulation
Test for Florida (Florida - HERS BESTEST)," Vol. 1 &
2, NREL/TP-550-23124, National Renewable Energy Laboratory,
Golden, CO.
- Fairey, P. et.al., January 1998.
"Comparison of EnGauge 2.0 Heating and Cooling Load
Predictions with the HERS BESTEST Criteria,"
FSEC-CR-893-98, Florida Solar Energy Center, Cocoa, FL.
- Guidelines for Uniformity: Voluntary
Procedures for Home Energy Ratings, Version 2.0, August
1996. Home Energy Rating Systems (HERS)
Council, Washington, DC.
- Florida
Building Energy Efficiency Ratings Act. §553.990,
Florida Statutes, 1993 et. seq.
- Florida Building Energy Rating System. Rule
9-B-60, Florida Administrative Code, Department of Community
Affairs, Office of Codes and Standards, Tallahassee, FL.
- Energy Efficiency Code for Building
Construction, 1997 Edition. Florida Department of
Community Affairs, Codes and Standards Office, Tallahassee,
Florida.
|